Metering Current Transformer
Metering Current Transformers (CTs) are used with measuring instruments, such as ammeters, voltmeters, kilowatt-hour meters, etc to Isolate the instruments from the power circuits
Accuracy Class
As per IEC standard: It is specify as Class 5, 3, 1, 0.5 0.2 and class 0.1
Class 5 & 3 is suitable for use in moving magnet analog metering.
Class 1 to class 0.5 is suitable for use with solid state digital metering.
Class 0.2, 0.2S, 0.5S & 0.5 are for revenue purpose. As indicated in the graphs below, class 0.2S & 0.5S CT is linear from 20% to 120% load. With extended low load accuracy up to 1.0%.
* Accuracy Limits Range: IEC std. requires that for class 0.1 to 1.0 CT, the minimum burden of measurement shall be 25% of its rated burden, subject to 1.0VA min.
e.g. A 15VA Class 1.0 CT is supposed to maintain its class 1 accuracy from 15VA to 3.75VA.
The below graphs indicate the accuracy and phase displacement for metering CT from class 0.1 to class
Class 5 & 3 is suitable for use in moving magnet analog metering.
Class 1 to class 0.5 is suitable for use with solid state digital metering.
Class 0.2, 0.2S, 0.5S & 0.5 are for revenue purpose. As indicated in the graphs below, class 0.2S & 0.5S CT is linear from 20% to 120% load. With extended low load accuracy up to 1.0%.
* Accuracy Limits Range: IEC std. requires that for class 0.1 to 1.0 CT, the minimum burden of measurement shall be 25% of its rated burden, subject to 1.0VA min.
e.g. A 15VA Class 1.0 CT is supposed to maintain its class 1 accuracy from 15VA to 3.75VA.
The below graphs indicate the accuracy and phase displacement for metering CT from class 0.1 to class
The below graphs indicate the accuracy and phase displacement for metering CT from class 0.2S to class 0.5S
Instrument Security Factor
Instrument Security Factor (FS): Usually 5 or 10.
It is similar to ALF in the case of protection CT. It is burden dependent.
In the event of system fault currents flowing through the primary winding of a CT, the safety of the apparatus supplied by the transformer is greatest when the value of FS is small.
Example: 400/5A class 0.5 metering CT is to be installed, FS required is <5.
A digital power-factor meter with burden of 0.5VA and an analog meter of 1.25VA are to be connected in series, 2.5mm2 pilot wires of 2M length is required:
The total burden is: 0.5 +1.25+ 0.75 = 2.5VA
For a 5A Sec. CT. 3.75 – 7.5VA CT maybe selected for used.
** 15VA CT is not suitable, as the accuracy range is from 15 to 3.75VA. - Out of range.
**As the FS of a 15VA CT is around 5.0 at its rated burden. Its FS at 2.5VA may be greater than 10. - Less protection.
** Oversize metering CT using low grade material will usually have high FS value.
It is similar to ALF in the case of protection CT. It is burden dependent.
In the event of system fault currents flowing through the primary winding of a CT, the safety of the apparatus supplied by the transformer is greatest when the value of FS is small.
Example: 400/5A class 0.5 metering CT is to be installed, FS required is <5.
A digital power-factor meter with burden of 0.5VA and an analog meter of 1.25VA are to be connected in series, 2.5mm2 pilot wires of 2M length is required:
The total burden is: 0.5 +1.25+ 0.75 = 2.5VA
For a 5A Sec. CT. 3.75 – 7.5VA CT maybe selected for used.
** 15VA CT is not suitable, as the accuracy range is from 15 to 3.75VA. - Out of range.
**As the FS of a 15VA CT is around 5.0 at its rated burden. Its FS at 2.5VA may be greater than 10. - Less protection.
** Oversize metering CT using low grade material will usually have high FS value.